Generator Sizing Calculator

Screen running and estimated motor-starting loads. Final generator selection requires manufacturer transient data and a complete load assessment.

How the calculation works

This calculator provides a preliminary load screen only and does not recommend a generator size. Starting demand is estimated as other running loads plus the selected motor running watts multiplied by a user-selected factor. Actual selection requires motor nameplate locked-rotor current/kVA, starting method, alternator transient curves, allowable voltage/frequency dip, load sequence, environmental derating and manufacturer sizing data. Verify the final design with the generator manufacturer and a qualified designer.

Worked example

Example: 6 kW running load and a 1.5 kW motor at 3× gives a rough 9 kW starting-load screen. This does not prove that any particular generator can start the motor.

Common mistakes to avoid

Frequently asked questions

Starting watts?

Prefer motor nameplate LRA/locked-rotor kVA and manufacturer data. Generic multiples are only rough screening assumptions and cannot select a generator.

Do generators need derating for altitude and heat?

Yes. Engine-driven units commonly lose about 3 to 4% of output per 1,000 ft of altitude and also derate in high ambient temperatures. Check the manufacturer's curves.

Is a generator rated in kW or kVA?

Both. Ratings are usually kW at 0.8 power factor, so kVA = kW ÷ 0.8.