Home › NEC / CEC Code › Wire Size & Ampacity Calculator (NEC 310.16)

Wire Size & Ampacity Calculator (NEC 310.16)

Find a preliminary conductor candidate from selected ampacity-table assumptions and adjustment factors. Final conductor and overcurrent-device selection requires additional installation and code checks.

How the calculation works

Start from NEC Table 310.16 ampacities (60/75/90°C). Multiply by the ambient correction factor (Table 310.15(B)(1), 30°C base) and the adjustment factor for more than three current-carrying conductors (310.15(C)(1): 4–6 = 80%, 7–9 = 70%, 10–20 = 50%, 21–30 = 45%, 31–40 = 40%, 41+ = 35%). Continuous loads are sized at 125% (210.19(A)(1), 215.2(A)(1)). With 90°C conductors, the unadjusted 75°C ampacity must still cover the load for typical terminations (110.14(C)). Cu 14/12/10 AWG are capped at 15/20/30 A and Al 12/10 AWG at 15/25 A by 240.4(D). Overcurrent protection is rounded to the next standard size in 240.6(A).

Worked example

Example: a 40 A load and a 0.80 conductor-count adjustment gives a 40 A adjusted value from a 50 A table entry. This example alone does not establish final conductor or overcurrent-device compliance; check all termination and installation limits.

Common mistakes to avoid

Frequently asked questions

Why does 90°C wire not allow 90°C ampacity?

Most terminals are rated 60 or 75°C. 90°C ampacity can be used for derating, but the final current is limited to the terminal rating.

CEC differences?

CEC Table 1–4 and Rule 4-004 differ slightly from NEC 310.16. Verify with the CEC for Canadian work.

Is 12 AWG copper always a 20 A circuit?

Under NEC 240.4(D), overcurrent protection for 12 AWG copper is generally limited to 20 A even though the 90°C column shows 30 A.

Can I use aluminum for branch circuits?

Yes, with terminations listed for aluminum. Aluminum needs a larger size than copper for the same load.

Read the guide

How to Size Wire for a 50 Amp Circuit (NEC) · 15 Amp vs 20 Amp Circuits: Wire Size, Receptacles and When to Use Each · Subpanel Wire Size: Feeder Conductors, Breakers and Grounds · How Many Outlets Can You Put on a Circuit? NEC Rules and Practical Limits

Related calculators

For informational and educational purposes only. Always consult a licensed electrician and local code authority. See our Electrical & Legal Disclaimer. Found an error? Tell us.