How the calculation works
I = W/V; VD = 2·I·L·R/1000 with R in Ω/1000 ft (copper at 20°C, NEC Chapter 9 Table 8). This model treats the total load as a point load at the far end; LED strips are often distributed loads, so long runs may have a different real voltage drop. Consider power injection and manufacturer guidance. Class 2 circuits fall under NEC Article 725 (CEC Section 16). Limit drop to 3–5% for even brightness.
Worked example
60 W @ 12 V = 5 A over 16 ft of 14 AWG: 0.40 V (3.4%).
Common mistakes to avoid
- Powering a long strip from one end only.
- Using wire that is too thin for the current.
- Ignoring the strip's own maximum run length.
Frequently asked questions
Fix dimming?
Use heavier wire, feed from both ends, or a higher voltage (24 V halves the current).
What is the maximum run for a 12 V strip?
Many strips are specified for about 16 ft (5 m) per feed regardless of wire size, because of the strip's own copper traces.
Why use 24 V instead of 12 V?
For the same watts, current is halved, which cuts the percentage voltage drop to about one quarter on the same wire.