LED & Low-Voltage Drop Calculator

Calculate voltage drop for 12 V and 24 V LED strips and find the longest run before dimming appears.

Important: Results are estimates based on the inputs and simplified assumptions shown. They are not a substitute for the adopted code, equipment instructions, site-specific engineering, or review by a qualified electrician.

How the calculation works

I = W/V; VD = 2·I·L·R/1000 with R in Ω/1000 ft (copper at 20°C, NEC Chapter 9 Table 8). This model treats the total load as a point load at the far end; LED strips are often distributed loads, so long runs may have a different real voltage drop. Consider power injection and manufacturer guidance. Class 2 circuits fall under NEC Article 725 (CEC Section 16). Limit drop to 3–5% for even brightness.

Worked example

60 W @ 12 V = 5 A over 16 ft of 14 AWG: 0.40 V (3.4%).

Common mistakes to avoid

Frequently asked questions

Fix dimming?

Use heavier wire, feed from both ends, or a higher voltage (24 V halves the current).

What is the maximum run for a 12 V strip?

Many strips are specified for about 16 ft (5 m) per feed regardless of wire size, because of the strip's own copper traces.

Why use 24 V instead of 12 V?

For the same watts, current is halved, which cuts the percentage voltage drop to about one quarter on the same wire.