Home › Load & Power › Single-Phase & Three-Phase Power Calculator

Single-Phase & Three-Phase Power Calculator

Convert voltage and current into kW, kVA and kVAR for single-phase and three-phase systems, with power factor and efficiency, so you can size transformers, generators and feeders correctly.

Important: Results are estimates based on the inputs and simplified assumptions shown. They are not a substitute for the adopted code, equipment instructions, site-specific engineering, or review by a qualified electrician.

How the calculation works

Single-phase: kVA = V·I/1000; three-phase: kVA = 1.732·V·I/1000 (V = line-to-line). kW = kVA·PF, kVAR = √(kVA² − kW²).

Worked example

3Φ, 480 V, 50 A, PF 0.85: 41.57 kVA, 35.3 kW, 21.9 kVAR.

Common mistakes to avoid

Frequently asked questions

Which voltage for 3Φ?

Line-to-line (e.g. 208, 480).

Why is the three-phase factor 1.732?

It is √3, which comes from the 120° phase shift between line-to-line voltages in a balanced three-phase system.

What is a typical motor power factor?

Lightly loaded induction motors can run between roughly 0.3 and 0.6; fully loaded motors are usually 0.8 to 0.9. Use nameplate data when you have it.

Related calculators

For informational and educational purposes only. Always consult a licensed electrician and local code authority. See our Electrical & Legal Disclaimer. Found an error? Tell us.