Home › Motor & Transformer › Motor Full-Load Current Calculator (NEC 430)

Motor Full-Load Current Calculator (NEC 430)

Look up full-load current from NEC Tables 430.248 and 430.250, then get the minimum conductor and maximum short-circuit protection for the motor.

How the calculation works

Full-load currents are from NEC Table 430.248 (single-phase) and 430.250 (three-phase). Branch-circuit conductors are sized at 125% of FLC (430.22) using the 75°C column. Short-circuit/ground-fault protection has specific percentage limits and exceptions under the adopted code; this tool no longer selects breaker or fuse sizes. Overload protection (430.32) is separate, typically 115–125% of nameplate current. Use nameplate current for overloads; this tool does not size starting or high-efficiency motors beyond the tables.

Worked example

10 HP, 3-phase, 460 V: table FLC = 14 A; 125% conductor-current screen = 17.5 A. These figures do not select a final conductor, breaker, fuse or overload. Apply installation derating, terminal limits, nameplate overload rules and the applicable code exceptions.

Common mistakes to avoid

Frequently asked questions

Do I use nameplate or table FLC?

Use the table FLC for conductor and short-circuit sizing; use the nameplate for overload protection.

When can maximum sizes be exceeded?

If the motor will not start, 430.52(C)(1) Exceptions allow higher ratings (up to 400% for breakers in some cases).

How is motor overload protection sized?

Per 430.32, typically 125% of nameplate current for motors with a 1.15 service factor or a 40°C rise or less, and 115% for others.

What about motors on variable frequency drives?

Use the drive's input current ratings and the Article 430 Part X rules, not these tables alone.

Read the guide

Motor Circuit Sizing Under NEC Article 430: A Worked Example

Related calculators

For informational and educational purposes only. Always consult a licensed electrician and local code authority. See our Electrical & Legal Disclaimer. Found an error? Tell us.