Home › Motor & Transformer › Transformer Sizing & Protection Calculator

Transformer Sizing & Protection Calculator

Convert transformer kVA to primary and secondary current and see the maximum overcurrent protection under NEC 450.3(B).

How the calculation works

The calculator estimates full-load current: I = kVA·1000 / (1.732·V) (balanced 3Φ) or kVA·1000 / V (1Φ). It does not select primary or secondary protective devices. Actual protection depends on transformer type, protection arrangement, current thresholds, conductors, terminals, code edition and applicable exceptions. Verify with the adopted NEC/CEC and a qualified designer.

Worked example

75 kVA, 3Φ 480→208 V: primary 90.2 A, secondary 208.2 A. These are full-load current estimates only, not breaker or conductor selections.

Common mistakes to avoid

Frequently asked questions

Conductors?

Conductor sizing and protective-device selection require the adopted code, transformer configuration, terminal ratings and applicable rules; this calculator does not select them.

What kVA do I need for a 100 A load at 208 V three-phase?

kVA = 1.732 × 208 × 100 ÷ 1000 ≈ 36 kVA, so select the next standard size (37.5 kVA or larger).

Do I add margin for future load?

Often yes. Size for expected growth and check the conductors on both sides.

Related calculators